Leak detection sensor MAXIMAT LWC BX
- Article code
- 41.1.38
- Description
- Leak detection sensor MAXIMAT LWC BX
- Material
- Completely in plastic
- More information
The leak sensor MAXIMAT LWC BX is mounted directly on the bottom of sump trays or rooms. Due to the low detection height of 1 mm, the leak detector notices even the smallest leaks.
Key features:
- Approval number DIBT:Z-65.40-496
- Integrated measuring transducer with test connection
- No moving parts
- Universally applicable even with SPS or signal processor - MAXIMAT TC4
- Suitable for electrically conductive, non-flammable liquids
Technical data:
- Operating principle: capacitive- high-frequency, fail-safe
- Ambient temperature: -20...+60°C
- Operating pressure: atmospheric, 0.8 - 1.1 bar
- Terminal housing: PBT glass-fiber reinforced; protection class IP65 according to EN 60 529
- Supply voltage: 15 - 27VDC
- Power consumption: < 1W
- Cable: 6m PVC, 5x 0.34mm²
Outputs:
- Potential-free reed relay contact: (contact opens on alarm), U supply =50V AC/DC max, I =0.5A max, P =10VA max.
- Coupling possible with our signal box TC4 or TC1 or voltage converter CST.
- Additional features: Connection possibility for a test button (potential-free contact) with which the complete MAXIMAT LW CX electronics, the cabling, the connected control and alarm controls can be tested
can be tested.
Connection options:
- Signal device MAXIMAT TC1/TC4
- ...